RSI Objects: what they are and how they reach KRL

A reference for the objects you wire together in RSIVisual, written from the RSIPI side: what each one does, which KRL system variable it touches, and whether RSIPI has a method for it.

Source: the official RsiElements.chm object reference shipped with the RSI option package, cross-checked against KUKA's own example contexts and against what this project has run on a real KR 16-2. Descriptions here are written fresh rather than copied — consult the CHM itself for the authoritative wording, full parameter ranges and defaults.


1. How the pieces fit together

An RSI context is a dataflow graph. Objects are nodes with typed input and output ports; you connect them in RSIVisual and the controller evaluates the whole graph once per interpolation cycle — every 4 ms in #IPO_FAST, 12 ms in #IPO.

Three file types, and it matters which is which:

File Who reads it
.rsi RSIVisual. Stores parameters by name (value="ExitMoveCorr")
.rsi.xml The controller. Stores the same parameters by ordinal (ParamValue="4")
.rsi.diagram RSIVisual canvas layout. Nothing else ever reads it

That name/ordinal split is the single most dangerous thing in this format. A wrong ordinal is still valid XML, still loads, and produces no error — it just silently means a different thing. Two real cases from this project are called out below.

Each object type has an ObjTypeID — ETHERNET is 64, POSCORR is 27 — and the .rsi.xml identifies objects by that number. Note that some IDs are shared by a main-axis and external-axis pair (AXISCORR/AXISCORREXT are both 33), distinguished by an input or output offset instead.

Where KRL comes in

Most objects never appear in KRL at all. This surprises people. The graph runs on the controller and is wired in RSIVisual; a KRL program does not reference POSCORR1 or SUM3 by name. What KRL does is:

  1. Load, start and stop the context:
ret = RSI_CREATE("RSIPI_Joints.rsi", CONTID, TRUE)
ret = RSI_ON(#RELATIVE)        ; or #ABSOLUTE
RSI_MOVECORR()                 ; sensor-guided motion
ret = RSI_OFF()
ret = RSI_DELETE(CONTID)
  1. Exchange data through KRL system variables. This is the real answer to "how does it appear in KRL". An object like SEN_PREA doesn't appear as an object — it appears as $SEN_PREA[1], an ordinary KRL variable your program reads or writes. The objects are the bridge between those variables and the signal graph:
KRL variable Read into the graph by Written from the graph by
$IN[n] DIGIN —
$OUT[n] DIGOUT MAP2DIGOUT, SETDIGOUT, RESETDIGOUT
$ANIN[n] ANIN —
$ANOUT[n] ANOUT MAP2ANOUT
$SEN_PREA[n] SEN_PREA MAP2SEN_PREA
$SEN_PINT[n] SEN_PINT MAP2SEN_PINT
$OV_PRO OV_PRO MAP2OV_PRO
$TECHPAR_C[fg,i] (config DEF_Tech.C) —
$TECHPAR[fg,i] — (config DEF_Tech.T)

The pattern is consistent: a bare name reads a KRL variable into the graph, and MAP2<name> writes the graph's value back out to it.

That table is the complete set of KRL variables reachable through an object — every $ variable named anywhere in the object reference — plus the STATUS object, which exposes four more read-only:

Via STATUS Type= KRL variable
ProState_S / ProState_R $PRO_STATE (submit / robot interpreter)
Pro_Mode_S / Pro_Mode_R $PRO_MODE
Mode_Op $MODE_OP — T1 / T2 / AUT / EXT
IPO_Mode / IPO_Mode_C $IPO_MODE

IPO_State and Sensor return interpolator and sensor-interface state that have no direct KRL variable.

  1. Reset or retune objects at runtime. Parameters not marked "cannot be changed at runtime" — the Reset flags on I, PID, TIMER, IIRFILTER, GENCTRL especially — are settable from KRL. See the RSI manual for the parameter-access functions; RSIPI does not wrap them.

Objects with no KRL variable at all (SUM, PID, LIMIT, the whole maths and logic set) exist purely inside the graph. They need no support from anything — you wire them and they work.

$FLAG — free, already wired, and useful

The ETHERNET object's Flag parameter needs no channel and no object of its own. Every shipped RSIPI context sets Flag=1, so $FLAG[1] is live on your controller right now:

IF $FLAG[1] THEN
  ; TRUE means the RSI connection is INTERRUPTED - it is a fault flag,
  ; not a health flag. Bring the cell to a safe state here.
ENDIF

This is the cleanest way for a KRL program to notice the PC has gone away without waiting for the Timeout break-off.

The third class: INTERNAL declarations

Neither an object nor a channel — just a line in the Ethernet config. RSI reads the system variable directly and the value costs nothing:

<ELEMENT TAG="DEF_RIst" TYPE="DOUBLE" INDX="INTERNAL" />
Declared Carries
DEF_RIst / DEF_RSol Cartesian actual / setpoint position
DEF_AIPos / DEF_ASPos Axis actual / setpoint position
DEF_EIPos / DEF_ESPos External axis actual / setpoint
DEF_MACur / DEF_MECur Motor currents, main / external axes
DEF_Delay Late-packet counter
DEF_EStr Message string to the controller
DEF_Tech.C1-C6 / DEF_Tech.T1-T6 $TECHPAR_C / $TECHPAR generators

RSIPI's parser also understands ELPos, BMode, IPOSTAT and IPOC, which no shipped config declares. IPOC is handled specially (the timestamp); the other three are available if you declare them, though their exact semantics are in the RSI manual rather than the object reference, so confirm before relying on them.

⚠️ DEF_Tech.T1 is the one to avoid: generator 1 is reserved for RSI's own corrections (RSITECHIDX), and declaring it makes the ETHERNET object report RSIBad. Use generator 2 for PC→KRL commands.

Where RSIPI comes in

ETHERNET is the object that makes RSIPI possible. It carries up to 64 inputs and 64 outputs over UDP, named by the RSI_EthernetConfig file. So:

  • Anything wired into ETHERNET arrives in api.client.send_variables.
  • Anything wired out of ETHERNET is written from api.client.receive_variables.

RSIPI is object-agnostic. Wire any object's output to an ETHERNET channel and it appears as a tag automatically — no library change needed. Named methods (motion.update_cartesian(), io.set_output()) exist only for the common cases, and everything else is reachable via api.tools.update_variable() and the raw dictionaries.


2. Motion correction

The objects that actually move the robot. All of them apply a correction on top of the programmed path; none of them command an absolute position.

POSCORR — ID 27

Cartesian correction of the TCP with limiting. Inputs CorrX…CorrC (mm and degrees); output Stat reports 0 = no motion active, 1 = correcting,

1 = being limited.

Parameters LowerLimX/Y/Z, UpperLimX/Y/Z and MaxRotAngle cap this object's cumulative correction, not the per-cycle delta. KUKA's default is ±5 mm, which is why a move can stop dead at exactly 5.00 mm with no error anywhere — the correction has hit the cap and simply stops growing. RSIPI's shipped contexts raise this to ±50 mm / 45°.

The reference is explicit about the silence: "if an input exceeds the valid range, the corresponding maximum value is used." The controller clamps and reports nothing. AXISCORR behaves identically.

There is a second, separate limit, and it is not silent. The RSI manual: object-specific corrections are limited by default to ±5 mm / 5° and clamped; the overall correction is limited to ±6 mm / 6°, and if that is exceeded, signal processing is stopped. The overall limit is set by a POSCORRMON / AXISCORRMON object — and applies at its 6 mm default when the context has none. On the KR 16-2 (2026-09-10) a context with ±50 mm POSCORR limits and no monitor stopped every move past ~5 mm with KSS29000 POSCORR Permissible overall correction exceeded: RSI is stopped. Every shipped context now carries a monitor at 500 mm / 180°.

Stat says exactly when — and where — it is clamping

Stat is not the 0/1/>1 summary it looks like. Above 1 it is bit-coded:

Bit Meaning
B0 always 1
B1 / B2 / B3 reached lower limit in X / Y / Z
B4 / B5 / B6 reached upper limit in X / Y / Z
B7 reached MaxRotAngle

So Stat = 17 (0b00010001) means "correcting, and clamped at the upper X limit". Wire Stat to a spare ETHERNET channel and the silent truncation becomes visible from Python — arguably the most useful diagnostic in this whole reference, given how much time that failure mode cost during bring-up.

⚠️ It cannot be sent back over Ethernet. Stat was wired to a spare ETHERNET input in RSIPI_Max and the controller refused the context with RSI_CREATE: Circular linking (2026-09-10): anything derived from an ETHERNET output (RKorr → POSCORR → Stat) must not feed an ETHERNET input. KUKA's own examples route Stat into GREATER → STOP instead, which is the pattern to copy. monitoring.get_correction_limit_status() decodes the bits if you do get the value to the PC some other way, and returns None on every shipped context.

AXISCORR has the same output if you want the joint equivalent.

RSIPI: motion.update_cartesian(), move_cartesian_trajectory(), and the trajectory engine. Wired in every shipped context as RKorr.X…RKorr.C.

AXISCORR — ID 33

The same idea per axis: CorrA1…CorrA6 in degrees, with LowerLimA* / UpperLimA* (default ±5°) and a Stat output.

RSIPI: motion.update_joints(). In RSIPI_Joints and above as AKorr.A1…A6.

AXISCORREXT — ID 33, input offset 7

External axes E1–E6. Shares its ObjTypeID with AXISCORR; what distinguishes it is that its ports and parameters start at index 7 (LowerLimE1 is index 7, not 1).

⚠️ This object cannot bind on a robot with no external axes. The ETHERNET object then reports RSIBad at RSI_ON and the robot stops. This is the single reason RSIPI_Full does not run on a standard 6-axis cell.

RSIPI: motion.move_external_axis(). RSIPI_Full only.

POSCORRMON — ID 81 · AXISCORRMON — ID 82

Despite the name, these are not passive monitors. Each sets the ceiling for the overall correction — and that ceiling exists whether or not the object does: with no monitor in the context the system default of 6 mm / 6° applies, and exceeding it stops RSI with KSS29000. Their outputs report the correction applied so far — X…C for POSCORRMON, A1–A6 then E1–E6 for AXISCORRMON.

⚠️ Confirmed on the KR 16-2, 2026-09-10: RSIPI_Basic (±50 mm POSCORR, no monitor) stopped every move at ~5 mm; adding POSCORRMON1 at 500 mm fixed it. Every shipped context now has one (Joints and Max also AXISCORRMON1), and config_builder warns when a context lacks them. The objects need no wiring — parameters only.

⚠️ AXISCORRMON outputs 7–12 are the external axes, so wire only outputs 1–6 on a 6-axis robot.

RSIPI: monitoring.get_applied_correction() and get_applied_joint_correction(), in RSIPI_Max. These answer "did the robot actually do what I asked?", which a commanded value cannot — see the STOP entry below for why that matters.


3. Reading the robot

All of these are sources: no inputs, just outputs.

Object ID Returns Notes
POSACT 24 Cartesian position X,Y,Z,A,B,C plus Status/Turn Type: Measured (default), IPO, IPO_FLT, CF — see the timing note below
AXISACT 32 Axis angles A1–A6 Same Type choice
AXISACTEXT 32, offset 7 External axis positions E1–E6 External axes only
MOTORCURRENT 47 Motor current per axis [A] No parameters
MOTORCURRENTEXT 47, offset 7 External axis motor currents External axes only
GEARTORQUE 46 Gear torque per axis [Nm] Type: setpoint / precontrol / motor-side
GEARTORQUEEXT 46, offset 7 External axis gear torques External axes only
STATUS 62 One controller status value See below
OV_PRO 63 Program override $OV_PRO No parameters

⚠️ The Type choice is a time shift, not just a source. IPO is about 100 ms in the future relative to the drive interface and refreshed only every 12 ms, and is valid only for CP motions; IPO_FLT is about 40 ms ahead. Measured is the default and the one to use unless you specifically want a look-ahead.

You usually don't need POSACT or AXISACT. The Ethernet config can declare DEF_RIst, DEF_RSol, DEF_AIPos, DEF_ASPos, DEF_MACur with INDX="INTERNAL", which RSI reads straight from the system variables at no channel cost and with no object. Every shipped RSIPI context does this, as do KUKA's own examples.

A trap worth knowing: under RSI correction the setpoint never changes — only the actual position moves. Read RIst and AIPos, not RSol/ASPos, or corrections look like they aren't working. RSIPI's motion.get_current_joints() prefers AIPos for exactly this reason.

STATUS in detail

One object gives one status value, chosen by its Type parameter (RSI_StatusType, default IPO_State). Want both the operating mode and the interface state? That is two STATUS objects on two channels.

Type Returns
IPO_State Interpolator state — a bit field, see below
ProState_S / ProState_R $PRO_STATE of the submit / robot interpreter
Pro_Mode_S / Pro_Mode_R $PRO_MODE of the submit / robot interpreter
Mode_Op $MODE_OP — 1 T1, 2 T2, 3 AUT, 4 EXT
IPO_Mode / IPO_Mode_C $IPO_MODE — 1 Base, 2 TCP (advance / main run)
Sensor Sensor-interface state — the controller's own view of RSI

Sensor is the one to reach for. It reports the RSI interface's health directly, which nothing else exposes:

0 OFF 1 PRE_INIT 2 INIT 3 CYCLE 4 FREEZE
5 FREEZE_IGNORE 6 TERMINATE 7 TERMINATE_IGNORE 8 CLEAR_OFFSETS 9 ERROR

CYCLE is the healthy running state. ERROR on the wire would be the earliest, clearest signal that RSI is unhappy — better than inferring it from packet timing.

$PRO_STATE: 1 FREE, 2 RESET, 3 ACTIVE, 4 STOP, 5 END. $PRO_MODE: 1 ISTEP, 2 MSTEP, 3 PSTEP, 4 CSTEP, 5 BSTEP, 6 GO.

IPO_State bit flags: 1 ACTIVE, 2 CONTINUE, 4 STOP, 8 FSTOP, 16 GSTOP, 32 GSTOP_MOV, 64 CP (current move is Cartesian), 128 SMOOTH.

⚠️ Not shipped in any RSIPI context. Not because it lacks a default — it defaults to IPO_State — but because the .rsi.xml stores Type as a number, and the reference only ever prints names. Following the pattern confirmed twice elsewhere (list order, counting from 0) would make Mode_Op = 5 and Sensor = 8, but that is a prediction, not a fact, and a wrong enum ordinal is silent. Add the object in RSIVisual and read the number it writes — the same one-minute method that settled Word = 4.


4. Digital and analogue I/O

Object ID Direction KRL variable
DIGIN 29 read $IN[n]
DIGOUT 43 read $OUT[n] — reads back what is set
MAP2DIGOUT 14 write $OUT[n]
SETDIGOUT 12 write $OUT[n], sets on a rising edge and latches
RESETDIGOUT 13 write $OUT[n], clears on a rising edge and latches
ANIN 30 read $ANIN[n] (index 1–32)
ANOUT 44 read $ANOUT[n] — reads back what is set
MAP2ANOUT 15 write $ANOUT[n] (index 1–32)

RSIPI: io.set_output(), io.get_input(), io.pulse() for digital; io.read_analog() / io.set_analog() for analogue (RSIPI_Max).

How to actually use this

First, the one that catches everybody: DIGOUT does not switch an output on. It reads back the current state of one. Writing is MAP2DIGOUT. The naming rule is consistent across RSI — a bare name reads a KRL signal into the graph, MAP2<name> writes it back out. (ANOUT reads too; MAP2ANOUT writes.)

One signal, or several?

That single decision drives everything else.

You want DataSize Index means Value on the wire
One output/input Bit the signal number itself 0 or 1
8 / 16 / 32 at once Byte / Word / DWord a byte number a bitmask integer

For a single gripper on $OUT[5], use Bit with Index=5. No arithmetic, no bitmask, and io.set_output(5, True) addresses it by its real number.

Byte and word addressing

With anything wider than Bit, Index counts bytes, and byte b covers:

$OUT[b * 8 + 1]  …  through 8, 16 or 32 signals
Index Covers (Byte)
1 $OUT[1]–$OUT[8]
2 $OUT[9]–$OUT[16]
3 $OUT[17]–$OUT[24] (Word: –$OUT[32])
20 $OUT[153]–$OUT[160] (Word: –$OUT[168])

Measured on the KR 16-2 (2026-09-10): MAP2DIGOUT with Index=2, Word put bit 1 on $OUT[10], so the first signal is (Index − 1) × 8 + 1. This is why Index=3 does not touch $OUT[3], and why outputs so often look "dead". (The August bring-up read DIGIN1 Index=1, Byte as $IN[9]–[16], i.e. Index × 8 + 1 — the two objects may count differently, or that reading was wrong; re-measure DIGIN before relying on either.)

Reading the bitmask — right to left

One integer carries all eight states. The lowest signal number is the rightmost (least significant) bit. With Index=2:

Bit 7 6 5 4 3 2 1 0
Output $OUT[24] [23] [22] [21] [20] [19] [18] $OUT[17]

So the first three on is 0b00000111 = 7:

api.io.set_output(1, True)   #   1  0b00000001   $OUT[17]
api.io.set_output(2, True)   #   3  0b00000011   $OUT[17],[18]
api.io.set_output(3, True)   #   7  0b00000111   $OUT[17],[18],[19]

0b11100000 = 224 would be the top three — $OUT[22], [23], [24].

Note the channel number in set_output() is the bit position, not the $OUT number, whenever the object is byte- or word-addressed. Each call is a read-modify-write of the whole word, so all eight signals travel together in one channel and land in the same 4 ms cycle. That is the real reason to use byte/word addressing instead of eight separate Bit objects.

Signed vs unsigned

Byte_U is unsigned (0–255); Byte is signed (−128–127). With signed, any value with the top bit set comes back negative — all eight on reads as −1, and $OUT[24] alone as −128.

So read with Byte_U / Word_U. You cannot do the same when writing: MAP2DIGOUT offers only Bit, Byte, Word. Mixing them is fine — the bits on the wire are identical, only the interpretation of the returned number differs — so write Word and read back Word_U.

Analogue is simpler

ANIN / MAP2ANOUT have no DataSize: just Index, 1–32, addressing $ANIN[n] / $ANOUT[n] directly. One value per object.

api.io.read_analog()        # $ANIN[1]
api.io.set_analog(0.75)     # $ANOUT[1]

Confirm what you sent actually landed

Pair a writer with a reader on the same range — MAP2DIGOUT to drive, a DIGOUT at the same Index to read back — and the robot tells you the real state of its own outputs. That is what DoutW does in RSIPI_Joints, and it is the only way to check without walking to the pendant.

Latching, and why a gripper may want it

MAP2DIGOUT is level-driven: send FALSE and the output drops. SETDIGOUT and RESETDIGOUT act only on a rising edge and latch, so the output holds regardless of what happens afterwards. Point both at the same Index and you have a set/reset pair:

ETHERNET Out7 ──→ SETDIGOUT   (Index 5)   close
ETHERNET Out9 ──→ RESETDIGOUT (Index 5)   open
api.io.pulse(7, duration=0.05)   # close - latches ON
api.io.pulse(9, duration=0.05)   # open  - latches OFF

⚠️ This matters for holding a workpiece. With MAP2DIGOUT and HOLDON="0", losing the PC resets the output and the gripper opens mid-cycle. HOLDON="1" holds the last value, and a latch holds it no matter what — the robot keeps hold of the part and stops. Choose deliberately.

⚠️ Do not let both ends drive the same output. RSI writes it every 4 ms, so a KRL assignment to the same $OUT appears to do nothing. If the output is safety-interlocked, leave it to KRL and send intent instead (krl.write_sen_pint()), so the output keeps a single owner.

Types: three different ones, easily conflated

Take DIGIN reading $IN[n]. Three separate types are involved:

What Type Range
The Index parameter (the n) Int 1 – 4096, default 1
The object's Out1 value Int Width set by DataSize
$IN[n] in KRL BOOL, indexed by an INT as configured on the controller

Two things people trip over:

  • The output is an Int even for DataSize=Bit. A single input arrives as integer 0 or 1, not a Bool. That is why RSIPI's configs declare DiL as TYPE="LONG" rather than BOOL. ($IN[n] in KRL is a BOOL — the object converts.)
  • Index is Int in both cases, but counts different things. With DataSize=Bit it is the $IN/$OUT number directly. With any wider size it is a byte number, and the first signal covered is:

    $OUT[(Index - 1) * 8 + 1] … through + 8, 16 or 32

So Index=3, DataSize=Word starts at $OUT[17] and covers $OUT[17]–[32] (measured: Index=2 put bit 1 on $OUT[10], 2026-09-10). Index counts bytes from 1, matching the parameter's minimum of 1.

The same applies to ANIN/ANOUT (Index 1–32, no DataSize) and to SEN_PREA/SEN_PINT (Index 1–20), which are always single values.

⚠️ The Index / DataSize trap

DataSize decides how many consecutive signals an object covers, and it changes what Index means:

For DataSize Bit, Index is a bit index (≥1). For anything wider it is a byte index (≥0).

So MAP2DIGOUT with Index=3, DataSize=Word does not drive $OUT[3]. Byte 3 begins at output 17, so it drives $OUT[17]–$OUT[32] (RSIPI_Max ships this way; a gripper on $OUT[18] is set_output(2)). Outputs appearing "dead" is almost always this.

And there are two different DataSize enums, which is a live hazard when hand-editing a .rsi.xml:

Enum Used by Values, in the order the reference lists them
RSI_DataSize DIGIN, DIGOUT Bit, Byte_U, Byte, Word_U, Word, DWord
RSI_DataSizeX MAP2DIGOUT Bit, Byte, Word

The lists are the ordinals, counting from Bit=0, so Word is 4 in RSI_DataSize and 2 in RSI_DataSizeX.

Confirmed against RSIVisual (2026-09-09): setting a DIGOUT to Word and saving makes RSIVisual write ParamValue="4". The reference itself only ever prints names, so this is worth knowing rather than deducing — and it is the cheap way to settle any other enum: set it in RSIVisual, save, read the number out of the .rsi.xml.

DataSize="2" therefore means Word on a MAP2DIGOUT but Byte on a DIGOUT. Get it wrong and the file still loads, still runs, and quietly moves half as many bits as you think.

(Fixed 2026-09-09: DIGOUT4, the DoutW read-back in RSIPI_Joints and RSIPI_Max, said Word in its .rsi but encoded 2 — a signed Byte — in its .rsi.xml, so it read back only the low 8 bits of the 16-bit word MAP2DIGOUT1 writes. The hardware test that passed used values 3, 5 and 0, all inside a byte, so it could not have caught it. Now 4 in both contexts.

This is also the neatest way to find that class of error: open the context in RSIVisual and save it. RSIVisual regenerates the .rsi.xml from the name-based .rsi, so every ordinal is rewritten correctly and any hand-edited mistake simply disappears — it repaired this one on its own.)


5. Talking to the KRL program

Object ID Direction KRL variable
SEN_PREA 58 read $SEN_PREA[1..20] — real values
MAP2SEN_PREA 17 write $SEN_PREA[1..20]
SEN_PINT 57 read $SEN_PINT[1..20] — integers
MAP2SEN_PINT 16 write $SEN_PINT[1..20]
MAP2OV_PRO 25 write $OV_PRO — program override

These are the general-purpose channels between a KRL program and the sensor system. A KRL program writes $SEN_PREA[1] = 42.0; a SEN_PREA object with Index=1 picks it up and can pass it to ETHERNET, and Python sees it.

The technology parameters $TECHPAR_C[fg,idx] (main run, config tag Tech.Cnm) and $TECHPAR[fg,idx] (advance run, Tech.Tnm) work differently: they need no object at all, just an INDX="INTERNAL" declaration in the Ethernet config.

⚠️ Function generator 1 is reserved for RSI's own use (RSITECHIDX). Declaring DEF_Tech.T1 makes the ETHERNET object report RSIBad. Use generator 2 for PC→KRL commands, as KUKA's own example does.

RSIPI: krl.read_param() / write_param() for Tech; krl.read_sen_pint() / write_sen_pint() for $SEN_PINT; monitoring.get_override() / set_override() for override. $SEN_PREA is wired as SenP1–SenP3 in every shipped context.

⚠️ Give MAP2SEN_PREA its own ETHERNET channels. KUKA's example shares channels 1–3 with POSCORR, which means the values get rate-limited along with the corrections — sending 42.0 and reading back 0.5.


6. Control flow and safety

STOP — ID 18

Stops a motion on a rising edge of its Bool input. Mode chooses the reaction:

Mode Effect
InfoMessage message only
PathNormal path-maintaining stop
Velocity maximum braking
PathFast fast path-maintaining stop
ExitMoveCorr ends an RSI_MOVECORR() motion — the default

A second, optional parameter Channel (default 0) tells several STOP objects apart: "when a stop object is triggered, its channel value is stored as a global parameter, which can be used to tell the reason for stopping from KRL." So with two STOP objects on different channels, the KRL program can find out which one fired.

This is the only way to end a purely sensor-guided RSI_MOVECORR() from outside; without it the KRL program blocks until an operator cancels it.

⚠️ Unresolved in this project. A STOP object added to a working context made the controller silently stop applying every correction — RSI kept running perfectly at full packet rate with zero late packets and no error, and the only symptom was a pose that never changed. Removing it restored motion exactly. Mode=4 is confirmed correct against KUKA's CircleCorr example, so the cause is still open. RSIPI_Stop exists to test it, and examples/stop_test.py measures a real move before testing the stop, because that failure was indistinguishable from success at the network level.

MONITOR — ID 55

Streams up to 24 connected signals over Ethernet for visualisation (the SmartHMI RSIMonitor plugin). Refresh sends only every nth cycle, and Channel (1–8) groups signals logically or separates synchronously running containers. Separate from the ETHERNET object and not used by RSIPI.

TIMER — ID 40 · DELAY — ID 50 · SIGNALSWITCH — ID 59 · LIMIT — ID 39 · MINMAX — ID 49

Graph-internal control: a timer that raises a Bool when its time expires (KUKA's CircleCorr drives a STOP from one), a fixed signal delay, a two-path switch controlled by a Bool, a clamp between two limits, and running min/max across up to 10 inputs.


7. The Ethernet interface

ETHERNET — ID 64

Up to 64 inputs and 64 outputs exchanged as XML over UDP, once per cycle.

Parameter Meaning
ConfigFile The RSI_EthernetConfig file, which must live in C:\KRC\ROBOTER\Config\User\Common\SensorInterface
Timeout Cycles tolerated without an answer. KUKA's default is 10; RSIPI ships 100 (0.4 s at 4 ms)
Flag Index of a $FLAG reporting the link state. $FLAG[Index] == TRUE means "connection interrupted" — it is a fault flag, not a health flag. Default −1 (disabled); RSIPI's contexts set 1
Precision Decimal places in sent data (default 1, max 32). Received data is always parsed at full precision, so the PC may reply with as many decimals as it likes

The config file: tags are just variable names

An ELEMENT in the Ethernet config is a channel given a name:

<ELEMENT TAG="DiO" TYPE="LONG" INDX="8" HOLDON="1" />

TAG is an arbitrary name you choose. It becomes the literal XML element in the telegram — that line produces <DiO>3</DiO> on the wire. DiO is not an RSI keyword; it is simply what KUKA called it in their example, and RSIPI inherited the name. Rename it to Gripper and everything still works, because both ends read the same config file.

What gives the channel meaning is the wiring in the context: ETHERNET1 output 8 → MAP2DIGOUT1 → $OUT[17] (Max). The name carries no meaning to the controller.

The exception is INDX="INTERNAL". Those tags are reserved RSI names:

<ELEMENT TAG="DEF_RIst" TYPE="DOUBLE" INDX="INTERNAL" />

DEF_RIst means "Cartesian actual position", DEF_Delay means "late packet counter". RSI reads the system variable directly, so they need no object and no channel — but you cannot rename them.

Rule: numbered INDX → the name is yours. INDX="INTERNAL" → the name is RSI's.

Dotted tags group into one element

A dot makes the value an attribute of a shared element:

Config On the wire
TAG="DiO" <DiO>3</DiO>
TAG="DiO.A", .B, .C <DiO A="1" B="0" C="1" />

RSIPI parses the second as one variable with three values: {"DiO": {"A": …, "B": …, "C": …}}. That is the same mechanism behind <RKorr X="…" Y="…" Z="…" />.

Grouping is naming only — each sub-value is still its own RSI signal and needs its own INDX and its own wired object. To pack several signals into one channel, use DataSize (byte/word), not dotted tags.

Useful convention: name a group's members o1, o2, o3 and io.set_output(1, True) finds them automatically, since it looks for o<channel> in any RECEIVE group. Names like .A/.B work equally well on the wire but need io.toggle('DiO', 'A', True).

TYPE decides how the value is written

TYPE is carried through to the wire, so a value goes out as what it was declared to be:

TYPE Python On the wire
BOOL bool 1 / 0
LONG int 7
DOUBLE float 1.500000 (6 dp)
STRING str as-is

This holds for grouped values too. Until 2026-09-09 it did not: every attribute was forced through float(), so a grouped BOOL went out as A="1.000000". None of the shipped configs declare a grouped BOOL or LONG on the RECEIVE side, so nothing was affected in practice — but a hand-built config would have been the first to hit it, and a silently mistyped signal is the hardest kind of fault to find on a robot.

Startup and failure modes

⚠️ The exchange starts the instant RSI_ON runs, so the PC must already be listening. Otherwise the object breaks off with RSIBad after Timeout cycles and the robot stops. RSIPI's RSIPI_Minimal.src HALTs before RSI_ON for this reason.

⚠️ A .rsi and a config from different builds gives RSI_CREATE: Invalid index - signal output — the graph references a channel the config never declares. Copy all four files together, and check first with examples/validate_context.py.

RSIPI can also generate the config from a context, which removes the commonest source of that mismatch:

python -m RSIPI.config_builder MyContext.rsi.xml --ip 10.10.10.10 --port 64000

8. Signal processing

None of these touch KRL or RSIPI. They are wired between objects inside the graph, and if you route one's output to an ETHERNET channel, RSIPI reads it as an ordinary number.

Sources and maths

Object ID Does
SOURCE 45 Signal generator: Const, Sin, Cos, Square, Sawtooth (default Const), with Offset, Amplitude and Period. Drives motion with no sensor attached
SUM 31 Adds up to 5 signals plus a constant
MULTI 42 Multiplies two signals
ABS POW EXP LOG NORM 48, 68, 76, 77, 83 Absolute value, power, e^x, ln, vector norm
ROUND CEIL FLOOR 80, 78, 79 Rounding to n places, up, down
SIN COS TAN ASIN ACOS ATAN ATAN2 69–75 Trigonometry, in degrees

Controllers and filters — the classical control blocks, all discretised against the sensor cycle:

Object ID Does
P 28 Gain
I 34 Integrator, with anti-windup limits and a KRL-settable Reset
D 67 Differentiator
PD 35 Proportional-differential
PID 36 Full PID
PT1 PT2 37, 38 First and second order lag
IIRFILTER 60 Bessel / Butterworth / Chebyshev, high or low pass
GENCTRL 56 Generic filter to 8th order, coefficients A1–A8/B0–B8

Logic, comparison and bitwise — up to 10 inputs each where it makes sense:

Object ID Does
AND OR XOR NOT 8, 9, 11, 10 Boolean logic
GREATER LESS 6, 5 Compare against a constant or another signal. Hysteresis sets the minimum difference before the output flips back, which stops a noisy signal chattering
EQUAL 7 Compare with a tolerance
BAND BOR BCOMPL 52, 53, 54 Bitwise and / or / complement on integers

Transformations

Object ID Does
TRAFO_USERFRAME 65 Transforms a 3-vector into a frame with a given offset and rotation
TRAFO_ROBFRAME 66 Transforms between robot reference frames (Base, TCP, …)

9. Rules learned the hard way

  1. A .rsi and its config are one unit. Always copy .rsi, .rsi.xml, .rsi.diagram and the config together.
  2. Never trust an enum ordinal you inferred. The .rsi stores names, the .rsi.xml stores numbers, and a wrong number is silent. Let RSIVisual write them — opening a context and saving it regenerates every ordinal from the names, which is both the fix and the check.
  3. Verify a context change by measuring real motion. An object can load perfectly and disable exactly the thing you care about, with the network still looking flawless.
  4. Add one object at a time. Every addition beyond KUKA's proven example broke something during this project's bring-up.
  5. External-axis objects need external axes. They are the most common cause of RSIBad on a standard 6-axis robot.